EPA and F-Gas legal rules for AC installation in Ireland
Under Regulation (EU) 2024/573, enforced in Ireland by the EPA, every split air conditioner containing fluorinated refrigerants such as R32 must be installed, vacuum-tested and commissioned by an installer holding a current EU-recognised QQI F-Gas certificate and working for an F-Gas Registration (FGR)-registered company. DIY installation of split systems is illegal and voids the manufacturer warranty.
Why EU Regulation 2024/573 makes certified F-Gas commissioning mandatory for every split AC system fitted in Ireland.
Free, no obligation. One local installer prices it, not five.
- Regulation (EU) 2024/573binding EU F-Gas law in Ireland
- EPAIrish statutory enforcement body
- R32 (GWP 675)standard modern split refrigerant
- Not validpost-Brexit UK F-Gas certs in ROI

What Regulation (EU) 2024/573 requires from your installer
Split air conditioning systems are not hermetically sealed appliances. The indoor unit and outdoor condenser are connected on site with flared copper tubing, pressure-tested and evacuated before R32 fluorinated gas is released into the circuit. In Ireland, the Environmental Protection Agency (EPA) enforces Regulation (EU) 2024/573 alongside national F-Gas regulations.
- Personal QQI F-Gas certificate. The individual technician brazing, flaring, vacuuming or charging refrigerant must hold a valid EU-recognised QQI Level 5 F-Gas Special Purpose Award (Category I or II depending on charge weight).
- F-Gas Registration (FGR) company certificate. The contracting firm carrying out residential or commercial split installation must also hold an active Company F-Gas Certificate registered in Ireland.
- Proof of certified installer at point of sale. Irish wholesalers are legally barred from selling non-hermetically sealed split AC equipment to uncertified buyers without documented evidence that a certified company will install it.
- No UK F-Gas certificates post-Brexit. Certificates issued by UK bodies after Brexit are no longer recognised in the Republic of Ireland; verify Irish or EU-member certification before work begins.
Price my AC
Four quick taps and our price shows before we ask for a phone number. One local F-Gas installer rings you, not five.
Single-room wall split AC, 1 room, back-to-back outer wall: €1,400 to €2,300, supplied and fitted.
How the price is worked out
The range reflects going Irish supply-and-fit rates for R32 inverter split, multi-split, commercial cassette and concealed ducted systems, including indoor and outdoor units, standard copper pipework, trunking, core drilling, vacuum pressure test and EPA F-Gas commissioning. Extended runs through attics or internal rooms, whisper condensate pumps and dedicated RECI electrical spurs with weatherproof rotary isolators adjust the figure. Ask whether VAT applies at 13.5% or 23% under Revenue's two-thirds rule. Only an F-Gas installer who surveys your rooms gives a firm written quote.
Five commissioning steps every F-Gas engineer completes on install day
- Precision flared or brazed copper joints. Torque-wrenched flare nuts prevent slow pinhole refrigerant leaks over thermal cycles.
- Dry oxygen-free nitrogen pressure test. Lines are pressurised to manufacturer test bar (typically 40+ bar on R32) to prove mechanical integrity before vacuuming.
- Deep vacuum dehydration. A two-stage vacuum pump pulls the circuit below 500 microns and holds a standing vacuum decay check to remove moisture and non-condensables.
- Exact refrigerant weigh-in (where line length exceeds pre-charge). Measured to the gram on digital scales if copper lines exceed the outdoor unit's factory allowance (usually 5 m to 7.5 m).
- Signed commissioning & F-Gas record. Documents charge weight, CO₂ equivalent, test readings and serial numbers needed to keep manufacturer parts warranties valid.
Further AC reading
Condensate & electricsGravity drainage vs whisper pumps, fused spurs and RECI rotary isolators.
Outdoor noise & Class 2(d)43 dB(A) boundary cap under S.I. 342/2026, brackets and condenser siting.
AC installation costsFull Irish fitted price breakdown by room count, access and electrics.
Single-room split AC2.5 to 5.0 kW wall-mounted inverter splits for bedrooms and lounges.
Multi-split home ACOne outdoor condenser serving 2 to 4 rooms with separate controls.
VAT & grant contextRevenue's 13.5% vs 23% two-thirds VAT rule and Irish SEAI grant context.Answers before you book a survey
Can a plumber or general builder install my split air conditioner?
Only if they hold current EU-recognised QQI F-Gas personal certification and operate under an F-Gas Registration (FGR) certified company. Otherwise connecting refrigerant pipes is an offence under EPA F-Gas law.
What happens if an uncertified person fits my AC unit?
Aside from breaching EU and Irish environmental law, poor flaring or skipped vacuuming leaves moisture in the compressor oil, causing early burnout and immediately voiding the manufacturer warranty.
Is R32 refrigerant still legal for new Irish home AC installations?
Yes. R32 (GWP 675) is the standard modern low-GWP refrigerant used across single and multi-split domestic systems in Ireland under current Regulation (EU) 2024/573 timelines.
Do domestic single-split units need mandatory statutory leak inspections?
Small residential R32 splits containing under 7.4 kg of R32 (below 5 tonnes CO₂ equivalent) do not require statutory annual F-Gas leak logbooks, though annual coil servicing is recommended for hygiene and warranty cover.
Every AC system, guide and county page
AC system types
Costs, sizing & rules

Check your room price before booking a survey
Pick the AC setup, room count and pipe run access. When you want a written site quote, your outline goes to a single F-Gas certified installer in your county.